Learning Advanced Features
Grou
p
Code
Name
LCD Display
Setting
Setting Range
Unit
41
Bypass selection
Regul Bypass
0: No
0
No
-
1
Yes
42
Number of auxiliary
motors
Num of Aux
5
1
AuxMaxMotor
2
-
43
3
Auxiliary starting
motor selection
Starting Aux
1
1–5
-
44
Number of operating
auxiliary motors
Aux Motor
Run
-
-
-
45
Auxiliary motor (#1 4)
priority
Aux Priority 1
-
-
-
46
Auxiliary motor (#5 8)
priority
Aux Priority 2
-
-
-
48
Auxiliary motor
operation at stop
Aux All Stop
0: No
0
No
-
1
Yes
49
Stop order for auxiliary
motors
FIFO/FILO
0: FILO
0
FILO
-
1
FIFO
2
Op Time
Order
50
Auxiliary motor
pressure difference
Actual Start
Diff
2
0–100
Unit
51
Main motor
acceleration time
when auxiliary motor #
is reduced
Aux Acc Time
2
0–600.0
Sec
52
Main motor
deceleration time
when auxiliary motor
is added
Aux Dec
Time
2
0–600.0
Sec
2
If Extension IO option is equipped or AP1-40 is set to 2 or 3‘, AuxMaxMotor is set to8.
Otherwise AuxMaxMotor is set to5‘.
3
If AP1-49 is set to 2(Op Time Order)‘, the parameter cannot be set by a user and it is
automatically changed as the operation time of aux motors.