Learning Advanced Features
262
Grou
p
Code
Name
LCD Display
Setting
Setting Range
Unit
53
Auxiliary motor start
delay time
Aux Start DT
5
0.0999.9
Sec
54
Auxiliary motor stop
delay time
Aux Stop DT
5
0.0999.9
Sec
55
Auto change mode
selection
Auto Ch
Mode
0: None
0
None
-
1
AUX
Exchange
2
MAIN
Exchange
56
Auto change time
Auto Ch Time
72: 00
00: 0099: 00
Min
57
Auto change
frequency
Auto Ch
Level
20.00
Low Freq–High
Freq
Hz
58
Auto change
operation time
Auto Op Time
-
-
-
59
Auxiliary motor
pressure difference
Aux Stop Diff
2
0~100
Unit
60
Target frequency of
Aux Motor while Multi
Master is operating
Follower Freq
60.00
Low Freq~
High Freq
Hz
61
#1 auxiliary motor
start frequency
Start Freq 1
45
Low Freq–High
Freq
Hz
62
#2 auxiliary motor
start frequency
Start Freq 2
45
Low Freq–High
Freq
Hz
63
#3 auxiliary motor
start frequency
Start Freq 3
45
Low Freq–High
Freq
Hz
64
#4 auxiliary motor
start frequency
Start Freq 4
45
Low Freq–High
Freq
Hz
65
#5 auxiliary motor
start frequency
Start Freq 5
45
Low Freq–High
Freq
Hz
66
4
#6 auxiliary motor
start frequency
Start Freq 6
45
Low Freq–High
Freq
Hz
4
AP1-66~68 , AP1-75~77 and AP1-85~87 are displayed when Extension IO option is
equipped or AP1-40 is set to2 or 3.