Learning Advanced Features
178
5.8.4 PID Switching (PID Openloop)
When one of the multi-function terminals (IN-6571) is set to25 (PID Openloop) and is
turned on, the PID operation stops and is switched to general operation. When the terminal
turns off, the PID operation starts again.