Learning Advanced Features
248
Cooling Fan Control Detail Settings
Code
Description
ADV-64 Fan
Control
Settings
Description
0
During Run
The cooling fan runs when the power is supplied to
the inverter and the operation command is on. The
cooling fan stops when the power is supplied to the
inverter and the operation command is off. When the
inverter heat sink temperature is higher than its set
value, the cooling fan operates automatically
regardless of its operation status.
1
Always On
Cooling fan runs constantly if the power is supplied to
the inverter.
2
Temp
Control
With power connected and the run operation
command on: if the setting is in Temp Control, the
cooling fan will not operate unless the temperature in
the heat sink reaches the set temperature.
Note
Despite setting ADV-64 to 0 (During Run)‘, if the heat sink temperature reaches a set level by
current input harmonic wave or noise, the cooling fan may run as a protective function.
5.33 Input Power Frequency and Voltage Settings
Select the frequency for inverter input power. If the frequency changes from 60 Hz to 50 Hz,
all other frequency (or RPM) settings, including the maximum frequency, base frequency,
etc., will change to 50 Hz. Likewise, changing the input power frequency setting from 50 Hz
to 60 Hz will change all related function item settings from 50 Hz to 60 Hz.
Group
Code
Name
LCD
Display
Parameter
Setting
Setting Range
Unit
BAS
10
Input power
frequency
60/50 Hz
Sel
0
60 Hz
0–1
-