Learning Basic Features
122
4.13.3 User V/F Pattern Operation
The H100 inverter allows the configuration of user-defined V/F patterns to suit the load
characteristics of special motors.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
BAS
07
V/F pattern
V/F Pattern
2
User V/F
0–3
-
41
User Frequency
1
User Freq 1
15.00
0–Maximum
frequency
Hz
42
User Voltage 1
User Volt 1
25
0100%
%
43
User Frequency
2
User Freq 2
30.00
0–Maximum
frequency
Hz
44
User Voltage 2
User Volt 2
50
0100%
%
45
User Frequency
3
User Freq 3
45.00
0–Maximum
frequency
Hz
46
User Voltage 3
User Volt 3
75
0100%
%
47
User Frequency
4
User Freq 4
Maximum
frequency
0–Maximum
frequency
Hz
48
User Voltage 4
User Volt 4
100
0100%
%
User V/F pattern Setting Details
Code
Description
BAS-41 User Freq
1 BAS-48 User
Volt 4
Set the parameter values to assign arbitrary frequencies (User Freq x) for
start and maximum frequencies. Voltages can also be set to correspond
with each frequency, and for each user voltage (User Volt x).

Table of Contents