EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Jog Operation; Jog Operation 1-Forward Jog by Multi-Function Terminal

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
149
Learning Advanced Features
5.2 Jog Operation
The jog operation allows for a temporary control of the inverter. You can enter a jog
operation command using the multi-function terminals or by using the [ESC] key on the
keypad.
The jog operation is the second highest priority operation, after the dwell operation. If a jog
operation is requested while operating the multi-step, up-down, or 3-wire operation modes,
the jog operation overrides all other operation modes.
5.2.1 Jog Operation 1-Forward Jog by Multi-function Terminal
The jog operation is available in either forward or reverse direction, using the keypad or
multi-function terminal inputs. The table below lists parameter setting for a forward jog
operation using the multi-function terminal inputs.
Group
Code
LCD Display
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
11
Jog frequency
JOG
Frequency
10.00
0.00, Low
FreqHigh
Freq
Hz
12
Jog operation
acceleration time
JOG Acc Time
20.00
0.00–600.00
sec
13
Jog operation
deceleration time
JOG Dec Time
30.00
0.00–600.00
sec
IN
65
71
Px terminal
configuration
Px Define(Px:
P1P7)
6
JOG
0-55
-
Forward Jog Description Details
Code
Description
IN-65–71 Px Define
Select the jog frequency from P1- P7 and then select 6. Jog from IN-
65-71.
[Terminal settings for jog operation]

Table of Contents

Related product manuals