Learning Advanced Features
5.2 Jog Operation
The jog operation allows for a temporary control of the inverter. You can enter a jog
operation command using the multi-function terminals or by using the [ESC] key on the
keypad.
The jog operation is the second highest priority operation, after the dwell operation. If a jog
operation is requested while operating the multi-step, up-down, or 3-wire operation modes,
the jog operation overrides all other operation modes.
5.2.1 Jog Operation 1-Forward Jog by Multi-function Terminal
The jog operation is available in either forward or reverse direction, using the keypad or
multi-function terminal inputs. The table below lists parameter setting for a forward jog
operation using the multi-function terminal inputs.
0.00, Low
Freq– High
Freq
Jog operation
acceleration time
Jog operation
deceleration time
Px terminal
configuration
Forward Jog Description Details
Select the jog frequency from P1- P7 and then select 6. Jog from IN-
65-71.
[Terminal settings for jog operation]