Learning Protection Features
Set the cooling fan fault mode.
The inverter output is blocked and the fan trip is
displayed when a cooling fan error is detected.
When OUT-36 (Q1 Define) and OUT-31–35
(Relay1–5) are set to ‗8 (FAN Warning)‘, the fan
error signal is output and the operation
continues.
OUT-36 Q1 Define,
OUT-31–35 Relay1–
5
When the code value is set to ‗8 (FAN Warning)‘, the fan error signal is
output and operation continues. However, when the inverter‘s inside
temperature rises above a certain level, output is blocked due to
activation of overheat protection.
6.3.2 Low Voltage Fault Trip
When inverter input power is lost and the internal DC link voltage drops below a certain
voltage level, the inverter stops output and a low voltage trip occurs.
Low voltage trip
decision delay
time
Low Voltage Fault Trip Setting Details
If the code value is set to ‗11 (Low Voltage)‘, the inverter stops the output
first when a low voltage trip condition occurs, then a fault trip occurs after the
low voltage trip decision time elapses. The warning signal for a low voltage
fault trip can be provided using the multi-function output or a relay. However,
the low voltage trip delay time (LVT Delay time) does not apply to warning
signals.