Learning Protection Features
6.2.3 Inverter Overload Protection (IOLT)
When the inverter input current exceeds the rated current, a protective function is activated
to prevent damage to the inverter, based on inverse proportional characteristics.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
OUT
31
35
Multi-function relay
1–5
Relay 1–5
6
IOL
-
-
36
Multi-function
output 1
Q1 Define
Note
A warning signal output can be provided in advance by the multi-function output terminal before
the inverter overload protection function (IOLT) operates. When the overcurrent time reaches
60% of the allowed overcurrent (120%, 1 min; 140%, 5 sec), a warning signal output is provided
(signal output at 120%, 36 sec).
6.2.4 Speed Command Loss
When setting operation speed using an analog input at the terminal block, communication
options, or the keypad, speed command loss setting can be used to select the inverter
operation for situations when the speed command is lost due to the disconnection of signal
cables.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
PRT
11
Keypad command
loss operation
mode
Lost KPD
Mode
0
None
0
None
-
1
Warning
2
Free-
Run
3
Dec
12
Speed command
loss operation
mode
Lost Cmd
Mode
1
Free-Run
-
-
13
Time to determine
speed command
loss
Lost Cmd
Time
1.0
0.1120.0
sec
14
Operation
Lost Preset F
0.00
Start
Hz