Learning Advanced Features
released), and is used when operating the inverter with a push button.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
07
Command source
Cmd Source*
1
Fx/Rx - 1
0-11
-
IN
65
71
Px terminal
configuration
Px Define(Px:
P1P7)
16
3-Wire
0-55
-
To enable the 3-wire operation, the following circuit sequence is necessary. The minimum
input time (t) for 3-wire operation is 2 ms, and the operation stops when both forward and
reverse operation commands are entered at the same time.
P1
P5
CM
(1):FX
(6):JOG
P7 (16):3-Wire
[Terminal connections for 3-wire operation]
FX
RX
3-Wire
Freq.
[3- wire operation]
5.5 Safe Operation Mode
When the multi-function terminals are configured to operate in safe mode, operation
commands can be entered in the Safe operation mode only. Safe operation mode is used
to safely and carefully control the inverter through the multi-function terminals.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit