Learning Advanced Features
rotation type auto tuning where parameters are measured while the motor is rotating,
parameter values measured with static auto tuning may be less accurate. Inaccuracy of the
measured parameters may degrade the performance of operations. Therefore, run static-
type auto tuning by selecting 2 (All) only when the motor cannot be rotated (when gearing
and belts cannot be separated easily, or when the motor cannot be separated mechanically
from the load).
• If auto tunning operates without wiring the motor, ‗Rs Tune Err‘ or ‗Lsig Tune Err‘ warning
messages are displayed. It can be reset if you press ‗STOP/RESET‘ button of the keypad.
5.22 Time Event Scheduling
Time Event function enables the user to operate the inverter using the RTC (Real-Time
Clock) feature at certain times that the user would like to set. An RTC battery is installed on
the I/O board of the H100 inverter, and it lasts approximately 25,800 hours with the inverter
turned off, and 53,300 hours with the inverter turned on.
To use the Time Event, set the current date and time. Three parameters need to be set to
configure the Time event feature: Time Period Module, Time Event, and Exception Date.
Used to set the time of operation.
Used to set the time of operation.
Used to specify the exception date. Exception date has the highest
priority.
4 Time period Module types, 8 Time Event Module types, and 8 Exception day types can be
used to configure time events. The Time Event function works based on a series of
configuration using the modules listed in the table above.
01/01/2000 ~
12/31/2099
(Date)