311
Learning Advanced Features
Code
Description
OUT-3135 Relay1
5
Set relay output (Relay 1–5).
OUT-36 Q1 Define
Select output for multi-function output terminal (Q1). Q1 is open
collector TR output.
5.48.3 Multi-function Output Terminal Delay Time Settings
Set on-delay and off-delay times separately to control the output terminal and relay
operation times. The delay time set at codes OUT-5051 applies to multi-function output
terminal (Q1) and relay, except when the multi-function output function is in fault trip mode.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
OUT
50
Multi-function output
On delay
DO On Delay
0.00
0.00
100.00
sec
51
Multi-function output
Off delay
DO Off Delay
0.00
0.00
100.00
sec
52
Select multi-function
output terminal
DO NC/NO Sel
000000*
0011
bit
*Multi-function output terminals are numbered. Starting from the right (number 1), the
number increases to the left.
Output Terminal Delay Time Setting Details
Code
Description
OUT-50 DO On
Delay
When a relay operation signal (operation set in OUT 31–35, 36) occurs,
the relay turns on or the multi-function output operates after the time
delay set at OUT-50.
OUT-51 DO Off
Delay
When relay or multi-function output is initialized (off signal occurs), the
relay turns off or multi-function output turns off after the time delay set at
OUT-54.
OUT-52 DO
NC/NO Sel
Select the terminal type for the relay and multi-function output terminal.
By setting the relevant bit to 0, it will operate A terminal (Normally Open).
Setting it to 1 will operate B terminal (Normally Closed). Shown below in
the table are Relay 15 and Q1 settings starting from the right bit.
Item
B terminal
(Normal close)
A terminal
(Normal open)