Learning Advanced Features
When interlock is released, the auxiliary motor‘s priority becomes different. When Interlock
occurs at auxiliary motor #2, the priority is number 1>3>4>5>2. When it occurs at auxiliary
motor #1, the priority is number 3>4>5>2>1. The figure below shows the order of the
auxiliary motors activating depending on the priority (of Interlock occurring and releasing). In
the figure, the order is the same for FILO/FIFO, because the auxiliary motor turns on.
Max
Freq
Off
On
AP1-62
AP1-61
AP1-74
AP1-73
AP1-72
AP1-71
AP1-70
Interlock operation
Feedback
Interlock 1
Interlock 2
Aux Motor 1
Aux Motor 2
Aux Motor 3
Aux Motor 4
Aux Motor 5
In case that Operable Motor and Standby Motor are set to 3 and 2 each, it operates in the
order of Aux Motor 2 Aux Motor 4 Aux Motor 5.
5.44.5 Aux Motor Time Change