Learning Basic Features
4.15 Output Voltage Setting
Output voltage settings are required when a motor‘s rated voltage differs from the input
voltage to the inverter. Set BAS-15 to configure the motor‘s rated operating voltage. The set
voltage becomes the output voltage of the inverter‘s base frequency. When the inverter
operates above the base frequency, and when the motor‘s voltage rating is lower than the
input voltage at the inverter, the inverter adjusts the voltage and supplies the motor with the
voltage set at BAS-15 (motor rated voltage). If the motors rated voltage is higher than the
input voltage at the inverter, the inverter will supply the inverter input voltage to the motor.
If BAS-15 (motor rated voltage) is set to0‘, the inverter corrects the output voltage based
on the input voltage in the stopped condition. If the frequency is higher than the base
frequency, when the input voltage is lower than the parameter setting, the input voltage will
be the inverter output voltage.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
BAS
15
Motor rated
voltage
Rated Volt
0
0, 170480
V