Learning Advanced Features
298
Press regeneration prevention is used during press operations to prevent braking during the
regeneration process. If motor regeneration occurs during a press operation, motor operation
speed automatically goes up to avoid the regeneration zone.
Group
Code
Name
LCD Display
Paramete
r Setting
Setting Range
Unit
ADV
74
Select press
regeneration prevention
for press
RegenAvd Sel
0
No
0–1
-
75
Press regeneration
prevention operation
voltage level
RegenAvd
Level
350 V
200 V class:
300400 V
V
700 V
400 V class:
600800 V
76
Press regeneration
prevention
compensation
frequency limit
CompFreq
Limit
1.00 (Hz)
0.00–10.00 Hz
Hz
77
Press regeneration
prevention P-Gain
RegenAvd
Pgain
50.0 (%)
0 .0–100.0%
%
78
Press regeneration
prevention I gain
RegenAvd
Igain
500 (ms)
2030000 ms
ms
Press Regeneration Prevention Setting Details
Code
Description
ADV-74 RegenAvd
Sel
Frequent regeneration voltage from a press load during a constant
speed motor operation may force excessive stress on the brake unit,
which may damage or shorten brake life. To prevent this, select ADV-74
(RegenAvd Sel) to control DC link voltage and disable the brake unit
operation.
ADV-75 RegenAvd
Level
Set brake operation prevention level voltage when the DC link voltage
goes up due to regeneration.
ADV-76 CompFreq
Limit
Set an alternative frequency width that can replace actual operation
frequency during regeneration prevention.
ADV-77 RegenAvd
Pgain, ADV-78
RegenAvd Igain
To prevent regeneration zone, set P-Gain/I gain in the DC link voltage
suppress PI controller.