Learning Advanced Features
Press regeneration prevention is used during press operations to prevent braking during the
regeneration process. If motor regeneration occurs during a press operation, motor operation
speed automatically goes up to avoid the regeneration zone.
Select press
regeneration prevention
for press
Press regeneration
prevention operation
voltage level
Press regeneration
prevention
compensation
frequency limit
Press regeneration
prevention P-Gain
Press regeneration
prevention I gain
Press Regeneration Prevention Setting Details
Frequent regeneration voltage from a press load during a constant
speed motor operation may force excessive stress on the brake unit,
which may damage or shorten brake life. To prevent this, select ADV-74
(RegenAvd Sel) to control DC link voltage and disable the brake unit
operation.
Set brake operation prevention level voltage when the DC link voltage
goes up due to regeneration.
Set an alternative frequency width that can replace actual operation
frequency during regeneration prevention.
ADV-77 RegenAvd
Pgain, ADV-78
RegenAvd Igain
To prevent regeneration zone, set P-Gain/I gain in the DC link voltage
suppress PI controller.