Communication as the command source
To enable power-on resume, set COM-96 (PowerOn Resume) to ‗YES‘, and set DRV-06 to
‗3 (Int 485)‘ or ‗4 (Field Bus).‘ If the power input to the inverter is cut off due to a power
interruption, the inverter memorizes the run command, frequency reference, and the
acc/dec time settings at the time of power interruption. If COM-96 (PowerOn Resume) is set
to ‗Yes‘, the inverter starts operating based on these settings as soon as the power supply
resumes.
• To prevent a repeat fault trip from occurring, set CON-71 (speed search options) bit 4 the
same as bit 1. The inverter will perform a speed search at the beginning of the operation.
• If the speed search is not enabled, the inverter will start its operation in a normal V/F pattern
and accelerate the motor. If the inverter has been turned on without ‗reset and restart‘
enabled, the terminal block command must be first turned off, and then turned on again to
begin the inverter‘s operation.
Use caution when operating the inverter with Power-on Run enabled as the motor will begin
rotating when the inverter starts up.