Learning Advanced Features
190
Code
Description
the other signal is not received until the time set at AP2-45 elapses.
IN-65–71 P17
define
Sets one of the multi-functional terminals to 45 (Damper Open) to
enable damper operation.
OUT-3135 Relay
1–5
Sets one of the relay outputs to ‘33 (Damper Control) to provide a
relay output when the inverter run command is turned on.
Note
Damper operation is one of the essential system features that are available in both HAND and
AUTO modes.