341
Learning Protection Features
Group
Code
Name
LCD Display
Parameter
Setting
Setting range
Unit
93
Motor torque current
Current Trq
-
0~100.0
%
94
Function torque
current of broken belt
BrokenBelt Trq
10.0
0~100.0
%
95
Function Delay time
of broken belt
BrokenBelt Dly
10.0
10.0
S
After inverter is operating in the frequency over PRT-92 and current torque reaches the limit
set at PRT-94 and then it meets the conditions at the time above set PRT-95, Broken Belt is
activated.
[BrokenBelt Trq %]
Torque Current
[A]
t
Time count
[BrokenBelt Dly]
t
Broken Belt
Warning or Trip
t
[Current Trq %]
at [BrokenBelt Freq]
No action