Learning Advanced Features
308
Code
Description
15
Stop
Outputs a signal at operation command off, and when
there is no inverter output voltage.
16
Steady
Outputs a signal in steady operation.
17
Inverter
Line
Outputs a signal while the motor is driven by the
inverter line.
18
Comm Line
Outputs a signal when multi-function input terminal
(switching) is entered. For details, refer to 5.31Supply
Power Transition page on 246.
19
Speed
Search
Outputs a signal during inverter speed search
operation.
For details, refer to 5.27Speed Search Operation on
page 236.
20
Ready
Outputs a signal when the inverter is in stand by mode
and ready to receive external operation commands.
21
MMC
Used as a multi-motor control function. By configuring
the relay output and the multi-function output to MMC
and configuring the AP1-40AP1-92, it can conduct the
necessary operations for multi-motor control function.
22
Timer Out
A timer function to operate terminal output after a
certain time by using multi-function terminal block input.
For details, refer to 5.43Timer Settings on page 259.
23
Trip
Outputs a signal after a fault trip.
Refer to 5.45 Multi-function Output On/Off Control on
page 259 .
25
DB
Warn %ED
Refer to 0
Dynamic Braking (DB) Resistor Configuration on page
295.
26
On/Off
Control
Outputs a signal using an analog input value as a
standard.
Refer to 5.45 Multi-function Output On/Off Control on
page 259 .
27
Fire Mode
Outputs a signal when Fire mode is in operation.
28
Pipe Break
Outputs a signal when a pipe is broken.
29
Damper Err
Outputs a signal when damper open signal is not
entered. For more details, refer to 0
Damper Operation on page 188.
30
Lubrication
Outputs a signal when a lubrication function is in
operation.