307
Learning Advanced Features
Code
Description
4
FDT-4
The output signal can be separately set for acceleration
and deceleration conditions.
In acceleration: Operation frequency Detected
frequency
In deceleration: Operation frequency > (Detected
frequencyDetected frequency width/2)
Detected frequency width is 10 Hz. When the detected
frequency is set to 30 Hz, FDT-4 output is as shown in
the graph below.
5
Over Load
Outputs a signal at motor overload.
6
IOL
Outputs a signal when the inverter input current
exceeds the rated current and a protective function is
activated to prevent damage to the inverter, based on
inverse proportional characteristics.
7
Under Load
Outputs a signal at load fault warning.
8
Fan
Warning
Outputs a signal at fan fault warning.
9
Stall
Outputs a signal when a motor is overloaded and
stalled.
10
Over
Voltage
Outputs a signal when the inverter DC link voltage rises
above the protective operation voltage.
11
Low Voltage
Outputs a signal when the inverter DC link voltage
drops below the low voltage protective level.
12
Over Heat
Outputs signal when the inverter overheats.
13
Lost
Command
Outputs a signal when there is a loss of analog input
terminal and RS-485 communication command at the
terminal block.
Outputs a signal when communication power is present
and an I/O expansion card is installed. It also outputs a
signal when losing analog input and communication
power commands.
14
RUN
Outputs a signal when an operation command is
entered and the inverter outputs voltage.
No signal output during DC braking.