Multi-step Frequency Setting Details
Configure multi-step frequency 1–7.
Choose the terminals to setup as multi-step inputs, and then set the
relevant codes (IN-65–71) to 7 (Speed-L), 8 (Speed-M), or 9 (Speed-H).
Provided that terminals P5, P6, and P7 have been set to Speed-L, Speed-
M and Speed-H respectively, the following multi-step operation will be
available.
[An example of a multi-step operation]
Set a time interval for the inverter to check for additional terminal block
inputs after receiving an input signal.
After adjusting IN-89 to 100 ms and an input signal is received at P6, the
inverter will search for inputs at other terminals for 100 ms, before
proceeding to accelerate or decelerate based on the configuration at P6.