161
Learning Advanced Features
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
19
PID reference 2
auxiliary gain
PID Ref2 Aux
G
0.0
-200.0200.0
Unit
20
PID feedback
source selection
PID Fdb Src
0
V1
0–9
21
PID feedback
auxiliary source
selection
PID Fdb
AuxSrc
0
None
011
22
PID feedback
auxiliary mode
selection
PID Fdb
AuxMod
0
M+(G+A)
013
23
PID feedback
auxiliary gain
PID Fdb Aux
G
0.0
-200.0200.0
Unit
24
PID feedback
band
PID Fdb
Band
0
0–Unit Band
Unit
25
PID proportional
gain 1
PID P-Gain 1
50.0
0.0300.00
Unit
26
PID integral time
1
PID I-Time 1
10.0
0.0200.0
sec
27
PID differential
time 1
PID D-Time 1
0.00
0–1.00
sec
28
PID feed forward
gain
PID FF-Gain
0.0
0.01000.0
Unit
29
PID output filter
PID Out LPF
0.00
0–10.00
sec
30
PID output upper
limit
PID Limit Hi
100.00
PID Limit Lo
100.00
Unit
31
PID output lower
limit
PID Limit Lo
0.00
-100.00–PID
Limit Hi
Unit
32
PID proportional
gain 2
PID P-Gain 2
5.0
0.0300.00
Unit
33
PID integral time
2
PID I-Time 2
10.0
0.0200.0
sec
34
PID differential
time 2
PID D-Time 2
0.00
0–1.00
sec
35
PID output mode
setting
PID Out
Mode
0
PID Out
0–3
36
PID output
reverse
PID Out Inv
0
No
0–1

Table of Contents