Learning Advanced Features
Used when the output of the EPID controller changes too fast or the
entire system is unstable, due to severe oscillation. In general, a lower
value (default value=0) is used to speed up response time, but in
some cases a higher value increases stability. The higher the value,
the more stable the EPID controller output is, but the slower the
response time.
EPI-14 EPID1 Limit
Hi,
EPI-15 EPID1 Limit
Lo
Limits the output of the controller.
If EPID Out Inv is set to ‗Yes,‘ the difference (error) value between the
reference and the feedback is set as the feedback–reference value.
Sets the unit for the control variable.
0: CUST is a custom unit defined by the user.
Adjusts the scale to fit the unit selected at EPI-17 EPI1 Unit Sel.
EPI-19 EPID1 Unit
0 %
EPI-20 EPID1 Unit
Sets the EPID1 Unit 0% value and the EPID1 Unit 100% value as the
minimum and maximum values set at EPI1-17.