EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Page 210

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Advanced Features
196
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
16
Pump clean
mode 2
Pump Clean
Mode2
0: None
0
None
-
1
Start
2
Stop
3
Start & Stop
17
Pump clean
load setting
PC Curve
Rate
100.0
100.0–200.0
%
18
Pump clean
reference band
PC Curve
Band
5.0
0.0100.0
%
19
Pump clean
operation delay
time
PC Curve DT
60.0
0–6000.0
sec
20
Pump clean
start delay time
PC Start DT
10.0
0–6000.0
Sec
21
0 speed
operating time
at Fx/Rx
switching
PC Step DT
5.0
1.06000.0
Sec
22
Pump clean Acc
time
PC Acc Time
10.0
0–600.0
Sec
23
Pump clean
Dec time
PC Dec Time
10.0
0–600.0
Sec
24
Forward step
run time
Fwd Steady
T
10.0
1.06000.0
Sec
25
Forward step
run frequency
Fwd
SteadyFreq
30
0.00, Low Freq
High Freq
Hz
26
Reverse step
run time
Rev Steady T
10.0
1.06000.0
Sec
27
Reverse step
run frequency
Rev
SteadyFreq
30
0.00, Low Freq
High Freq
Hz
28
Number of
Fx/Rx steps for
pump clean
PC Num of
Steps
5
010
-
29
Pump clean
cycle monitoring
Repeat Num
Mon
-
-
-
30
Pump clean
repeat number
Repeat Num
Set
5
010
-

Table of Contents