Preparing the Installation
• If you are installing multiple inverters in one location, arrange them side-by-side and
remove the vent covers. Use a flat head screwdriver to remove the vent covers. Only
the H100 inverters rated for up to 30 kW may be installed side-by-side.
• The vent covers must be removed for side-by-side installations.
• Side-by-side installation cannot be used for the H100 inverters rated for 37 kW and above.
• For the H100 inverters rated for 37 kW and above, if the installation site satisfies the UL
Open Type requirements and there is no danger of foreign objects getting inside the inverter
and causing trouble, the vent cover may be removed to improve cooling efficiency.