207
Learning Advanced Features
Code
Description
PRT-73 LDT Dly
Time
Sets the delay time for the operation set at PRT-70.
PRT-74 LDT
Level
Sets the level for the level detection.
The following are the setting ranges and default values by the source.
Source
Default Value
Setting Range
Output
Current
Rated current
0–150% of the rated current
DC Link
Voltage
350
700
0–450 V (2 Type)
0–900 V (4 Type)
Output
Voltage
230
460
0–250 (2 Type)
0–500 (4 Type)
kW
90% of the Inverter
rated power
0–150% of the Inverter rated
power
V1
9.00 V
0.00–12.00
V2
9.00
-12.0012.00
I2
18.00
0.00–25.00
PID Ref
Value
50
PID Unit MinPID Unit Max
PID Fdb Val
50
PID Unit MinPID Unit Max
PID Output
50
-100.00%100.00%
EPID1 Fdb
Val
50
EPID1 Unit MinEPID1 Unit Max
EPID2 Fdb
Val
50
EPID2 Unit MinEPID2 Unit Max
PRT-75 LDT
Band
Width
If the source is detected below the set level, it must be adjusted to be
above the LDT Level + LDT Band Width value to release the level
detection fault trip.
If the source is detected above the set level, it must be adjusted to be
below theLDT Level - LDT Band Width‘ value to release the level detection
fault trip.
The level detection trip bandwidth is 10% of the maximum source value.
PRT-76 LDT
Freq
Sets the start frequency for the level detection. When setting the level
detection frequency, take into consideration the source type and the LDT
level.
PRT-77 LDT
Restart DT
If PRT-08 (RST restart) is set to YES, the inverter restarts after the time set
at PRT-76 elapses when an LDT trip is released. The LDT Restart operates
each time an LDT trip is released.
If PRT-77 is set to any other value than0 and the inverter is operating in
HAND mode, the inverter resets and the LDT trip is released. However, the
inverter stays in OFF mode and does not restart the operation instantly.
OUT-3135
Relay 15
Sets one of the output relays to 40 (LDT) to monitor the level detection
status.