277
Learning Advanced Features
AP1-61
AP1-62
AP1-63
AP1-64
AP1-65
Max Freq
Inverter
Out Freq
AP1-70
AP1-71
AP1-72
Aux Motor 1
Aux Motor 2
Aux Motor 3
Aux Motor 4
Aux Motor 5
Feedback
AP1-70
AP1-71
AP1-72
Perform Aux_Exch
Reset the [Auto Op Time]
AP1-62
AP1-63
AP1-64
0%
100%
Fx
Off
On
Priority of the moment
M2  M1  M3 /
M4  M5
Priority of the moment
M1  M2  M3 /
M4  M5
Priority of the moment
M3  M2  M1 /
M4  M5
Priority of the moment
M3  M2  M1 /
M4  M5
5min
10min
AP1-61
Priority of the moment
M4  M5  M3 /
M2  M1
30min
Operation time
M1(30min) / M2(25min) /
M3(20min)
AP1-73
Priority of the moment
M4  M5  M3 /
M2  M1
Motor to operate MMC : M1, M2, M3
Standby motor : M4, M5
Motor to operate MMC : M3, M4, M5
Standby motor : M1, M2
Supposing its operation in
less than 1 minute
AP1-74
AP1-72
AP1-65
Aux Auto Change operation (Op Time Order) when operable motor and standby motor are set to 3 and 2 each
Option 1: [AP1-58 Auto Op Time] >= [AP1-56: Auto Ch Time]
When AP1-55 (Auto Ch Mode) is set to 2 (Main Exchange), the system uses all the motors
(main and auxiliary motors) regardless of the types. The auxiliary motor with the highest
priority is operated first and used as the main motor. Then, when the auto change
conditions are met, this motor is stopped and the motor priorities are re-arranged. This way,
the system always operates the motor with the highest priority and uses it as the main
motor of the MMC operation. In this case, before auto change is operated for the main
motor, the interlock delay time set at AP1-91 (Interlock DT) is applied.