Learning Protection Features
Multi-function relay
1–5 item
Multi-function
output 1 item
Stall Prevention Function and Flux Braking Setting Details
Stall prevention can be configured for acceleration, deceleration, or while
operating a motor at constant speed.When the LCD segment is on, the
corresponding bit is off.
Stall protection during acceleration
Stall protection while operating at a
constant speed
Stall protection during deceleration
Flux braking during deceleration
Stall protection
during
acceleration
If inverter output current exceeds the preset stall
level (PRT- 52, 54, 56, 58) during acceleration,
the motor stops accelerating and starts
decelerating. If current level stays above the
stall level, the motor decelerates to the start
frequency (DRV-19). If the current level causes
deceleration below the preset level while
operating the stall protection function, the motor
resumes acceleration.
Similar to stall protection function during