RS-485 Communication Features
Maximum number
of BACnet
Masters
1) 1200 bps, 2400 bps, 4800 bps, 57600 bps, 115200 bps cannot be set in communication
speed setting in case of BACnet communication.
BACnet Parameter Setting Details
COM-01 Int485
ST ID(MAC ID)
Refers to MACID setting parameter used in BACnet. All MACIDs of the
inverter using BACnet must be set before connecting to BUS. MACID must
have the unique value from the Network to be connected to MACID. If
BACnet is used, the value must be within 0–127. Communication is not
available if the value is not included in the range.
Sets the communication speed to use in the network.
Range for Max Master that is the number of devices currently connected to
the communication Line is 1–127, and the default value is 127.
COM-21–22
BAC Dev Inst 1–
2
BACnet Device Instance is used to identify BACnet Device, and must be
set as the unique value in the BACnet network. It is used efficiently when
finding BACnet Device of other Devices while installing.
The following formula is used to calculate the Device Instance value:
(COM-21 X 1000) + COM-22
Therefore, in the Device Instance value, COM-21 takes the thousands and
higher places (fourth digit and over) and COM-22 takes the hundreds and
lower places (third digit and below).
COM-21 and COM-22 have the ranges of 0–4194 and 0–999 respectively,
because Device Instance can have the value within 0–4,194,302.
Refers to the password used for Warm/Cold Start. COM-23 Password