EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Page 408

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RS-485 Communication Features
394
Property
Object Type
Database Revision
O
Preset Value
O
O
O
O
O
O
Description
O
O
O
O
O
O
O
Status Flags
O
O
O
O
O
O
Event State
O
O
O
O
O
O
Reliability
O
O
O
O
O
O
Out-of-Service
O
O
O
O
O
O
Number of states
O
O
State text
O
O
Units
O
O
Polarity
O
Active Text
O
O
Inactive Text
O
O
* BI–Binary Input / BVBinary Value / AIAnalog Input / AVAnalog Value / MSI–Multistate
Input / MSVMultistate Value
You can read/write in Location and Description only if it is the device object. You can write a
maximum of 29 words.
7.4.5.1 Analog Value Object Instance
Instance ID
Object Name
Description
Setting Range
Units
R/W
AV1
CommTimeoutSet
Command timeout
setting
0.1120.0
Secs
R/W
AV2
AccelTimeSet
Accelerate time setting
0.0600.0
Secs
R/W
AV3
DecelTimeSet
Decelerate time setting
0.0600.0
Secs
R/W
AV4
CommandFreqSet
Command frequency
setting**
0.00DRV-20
Hz
R/W
AV5
PIDReferenceSet
PID reference setting
0–100.0
%
R/W
AV6
PIDFeedbackSet
PID feedback setting
0–100.0
%
R/W

Table of Contents

Related product manuals