RS-485 Communication Features
404
No.
Name
Unit
Description
AI6
Latch Trip Info2
-
Latch type fault trip information 2
(Refer to Common Area parameter address
0h0331)*
AI7
Latch Trip Info3
-
Latch type fault trip information 3
(Refer to Common Area parameter address
0h0335)*
AI8
Level Trip Info
-
Level‘ type fault trip information
(Refer to Common Area parameter address
0h0332)(1)
AI9
H/W Diagnosis Trip
Info
-
H/W Diagnosis fault trip information
(Refer to Common Area parameter address
0h0333)(1)
AI10
Warning Info
-
Warning information
(Refer to Common Area parameter address
0h0334)(1)
* Refer to 7.3.8Compatible Common Area Parameteron page 370.
7.5.3.4 Binary Input
Metasys-N2 master unit monitors the inverter input and output status in binary codes. The
following table lists the binary codes used and their meanings.
No.
Name
Description
BI1
Stopped
1 Stopped
BI2
Running Forward
1 Forward operation is running.
BI3
Running Reverse
1 Reverse operation is running.
BI4
Tripped
1 Fualt trip occurred.
BI5
Accelerating
1 Accelerating
BI6
Decelerating
1 Decelerating
BI7
Reached Full Speed
1 Running at a steady speed (frequency
refernece)
BI8
DC Braking
1 Running on DC power source
BI9
Stopping
1–Stopping is in progress.
BI10
P1 Input
1–True / 0 - False
BI11
P2 Input
1–True / 0–False