Table of Functions
413
Cod
e
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
value
Property*
Ref.
20
-
Auto
Tuning
Auto
Tuning
0
None
0: None
Δ
p.212
1
All
(Rotation
type)
2
All (Static
type)
3
Rs+
Lsigma
(Rotation
type)
21
-
Stator
resistor
Rs
0.0-999.9 ()
Depende
nt on
motor
setting
Δ
p.212
22
-
Leakage
inductance
Lsigma
0.000-9.999
(mH)
Δ
p.212
41
13
0h122
9
User
frequency1
User Freq 1
0.00 - Maximum
frequency (Hz)
15.00
Δ
p.122
42
0h122
A
User
voltage1
User Volt 1
0–100 (%)
25
Δ
p.122
43
0h122
B
User
frequency2
User Freq 2
0.00-Maximum
frequency (Hz)
30.00
Δ
p.122
44
0h122
C
User
voltage2
User Volt 2
0-100 (%)
50
Δ
p.122
45
0h122
D
User
frequency3
User Freq 3
0.00 - Maximum
frequency (Hz)
45.00
Δ
p.122
46
0h122
E
User
voltage3
User Volt 3
0-100 (%)
75
Δ
p.122
47
0h122
F
User
frequency4
User Freq 4
0.00 - Maximum
frequency (Hz)
60.00
Δ
p.122
48
0h123
0
User
voltage4
User Volt 4
0-100 (%)
100
Δ
p.122
50
14
0h123
Multi-step
Step Freq-1
Low Freq- High
10.00
O
p.100
13
BAS-41–48 are displayed when BAS-07 or M2-25 is set to 2 (User V/F)‘.