Table of Functions
418
Code
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Property*
Ref.
before
DC
braking
15
0h130
F
DC
braking
time
DC-Brake
Time
0.00- 60.00
(sec)
1.00
Δ
p.129
16
0h1310
DC
braking
rate
DC-Brake
Level
0–200 (%)
50
Δ
p.129
17
0h1311
DC
braking
frequency
DC-Brake
Freq
Startfrequency-
60 Hz
5.00
Δ
p.129
20
0h1314
Dwell
frequency
on
accelerati
on
Acc Dwell
Freq
Start frequency-
Maximum
frequency (Hz)
5.00
Δ
p.155
21
0h1315
Dwell
operation
time on
accelerati
on
Acc Dwell
Time
0.0-60.0 (sec)
0.0
Δ
p.155
22
0h1316
Dwell
frequency
on
decelerati
on
Dec Dwell
Freq
Start frequency-
Maximum
frequency (Hz)
5.00
Δ
p.155
23
0h1317
Dwell
operation
time on
decelerati
on
Dec Dwell
Time
0.0-60.0 (sec)
0.0
Δ
p.155
24
0h1318
Frequenc
y limit
Freq Limit
0
No
0: No
Δ
p.133
1
Yes
25
0h1319
Frequenc
y lower
limit value
Freq Limit
Lo
0.00-Upper limit
frequency (Hz)
0.50
Δ
p.133
26
0h131
Frequenc
Freq Limit
Lower limit
Max freq
Δ
p.133

Table of Contents