Table of Functions
421
Code
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Property*
Ref.
67
0h1343
Output
contact
On level
On-Ctrl
Level
Output contact
off level-
100.00%
90.00
Δ
p.290
68
0h1344
Output
contact
Off level
Off-Ctrl
Level
-100.00-
outputcontact
on level (%)
10.00
Δ
p.290
70
0h1346
Safe
operation
selection
Run En
Mode
0
Always
Enable
0:
Always
Enable
Δ
p.153
1
DI
Depend
ent
71
24
0h1347
Safe
operation
stop
options
Run Dis
Stop
0
Free-
Run
0: Free-
Run
Δ
p.153
1
Q-Stop
2
Q-Stop
Resum
e
72
0h1348
Safe
operation
decelerati
on time
Q-Stop
Time
0.0-600.0 (sec)
5.0
O
p.153
74
0h134
A
Selection
of
regenerati
on
evasion
function
for press
RegenAvdS
el
0
No
0: No
Δ
p.297
1
Yes
75
0h134
B
Voltage
level of
regenerati
on
evasion
motion for
press
RegenAvd
Level
200 V: 300-400
V
350
Δ
p.297
400 V: 600-800
V
700
24
ADV-7172 are displayed when ADV-70 is set to 1 (DI Dependent).