EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Page 443

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table of Functions
429
Cod
e
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Propert
y*
Ref.
55
0h1537
I2 maximum
input current
I2 Curr x2
0.00-24.00 (mA)
20.00
O
p.92
56
0h1538
Output at I2
maximum
current (%)
I2 Perc y2
0.00-100.00 (%)
100.00
O
p.92
61
0h153
D
I2 rotation
direction
options
I2 Inverting
0
No
0: No
O
p.92
1
Yes
62
0h153
E
I2 Quantizing
level
I2 Quantizing
0.00
37
0.04-10.00 (%)
0.04
O
p.92
65
0h1541
P1 Px terminal
configuration
P1 Define
0
None
1: Fx
Δ
p.10
2
1
Fx
66
0h1542
P2 Px terminal
configuration
P2 Define
2
Rx
2: Rx
Δ
p.10
2
67
0h1543
P3 Px terminal
configuration
P3 Define
3
RST
5: BX
Δ
p.33
9
68
0h1544
P4 Px terminal
configuration
P4 Define
4
External
Trip
3: RST
Δ
p.33
8
69
0h1545
P5 Px terminal
configuration
P5 Define
5
BX
7: Sp-L
Δ
p.33
8
70
0h1546
P6 Px terminal
configuration
P6 Define
6
JOG
8: Sp-M
Δ
p.14
9
71
0h1547
P7 Px terminal
configuration
P7 Define
7
Speed-L
9: Sp-H
Δ
p.10
0
8
Speed-M
p.10
0
9
Speed-H
p.10
0
11
XCEL-L
p.11
3
12
XCEL-M
p.11
3
37
* Quantizing is disabled if 0‘ is selected.

Table of Contents