Table of Functions
441
Cod
e
Comm.
Addres
s
Name
LCD
Display
Parameter Setting
Initial
Value
Property*
Ref.
02
0h1702
Built-in
communicat
ion protocol
Int485
Proto
0
ModBus
RTU
0:
ModBus
RTU
O
p.35
1
2
LS Inv 485
4
BACnet
5
Metasys-
N2
6
41
ModBus
Master
03
0h1703
Built-in
communicat
ion speed
Int485
BaudR
0
1200 bps
3: 9600
bps
O
p.35
1
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
56 Kbps
7
76.8 kbps
8
115.2
Kbps
42
04
0h1704
Built-in
communicat
ion frame
setting
Int485
Mode
0
D8/PN/S1
0:
D8/PN/S
1
O
p.35
1
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1
05
0h1705
Transmissio
n delay
after
reception
Resp
Delay
0-1000 (msec)
5
O
p.35
1
41
COM-02 is automatically set to 6(Modbus Master) when AP1-40 is set to2 or 3‘.