Table of Functions
461
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
Ref.
10
0h190A
EPID1
integral
time
EPID1 I-
Time
0.0200.0 (sec)
10.0
O
p.179
11
0h190B
EPID1
differentiati
on time
EPID1 D-
Time
0.00–1.00 (sec)
0.00
O
p.179
12
0h190C
EPID1
feed-
forward
gain
EPID1 FF-
Gain
0.01000.0 (%)
0.0
O
p.179
13
0h190D
EPID1
output
filter
EPID1 Out
LPF
0.00–10.00 (sec)
0.00
O
p.179
14
0h190E
EPID1
output
upper limit
EPID1
Limit Hi
EPID1 Limit Lo–
100.00
100.00
O
p.179
15
0h190F
EPID1
lower limit
EPID1
Limit Lo
-100.00–EPID1
Limit Hi
0.00
O
p.179
16
0h1910
EPID1
output
inverse
EPID1 Out
Inv
0
No
0: No
O
p.179
1
Yes
17
0h1911
EPID1 unit
EPID1
Unit Sel
Refer to the
EPID Unit details
table (p.179)
1: %
O
p.179
18
0h1912
EPID1 unit
scale
EPID1
Unit Scl
0
X100
2: X1
O
p.179
1
X10
2
X1
3
X0.1
4
X0.01
19
0h1913
EPID1 unit
0% value
EPID1
Unit0%
X100
-
30000
Unit
Max
Values
vary
depend
ing on
the unit
O