Table of Functions
465
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
Ref.
42
0h192A
EPID2
feed-
forward
gain
EPID2 FF-
Gain
0.01000.0 (%)
0.0
O
p.179
43
0h192B
EPID2
output
filter
EPID2 Out
LPF
0.00–10.00 (sec)
0.00
O
p.179
44
0h192C
EPID2
output
upper limit
EPID2
Limit Hi
EPID2 Limit Lo–
100.00
100.00
O
p.179
45
0h192D
EPID2
output
lower limit
EPID2
Limit Lo
-100.00–EPID2
Limit Hi
0.00
O
p.179
46
0h192E
EPID2
output
inverse
EPID2 Out
Inv
0
No
0: No
O
p.179
1
Yes
47
0h192F
EPID2 unit
EPID2
Unit Sel
Refer to EPID
Unit details table
(p.179)
0:
CUST
O
p.179
48
0h1930
EPID2 unit
scale
EPID2
Unit Scl
0
X100
2: X1
O
p.179
1
X10
2
X1
3
X0.1
4
X0.01
49
0h1931
EPID2 unit
0% value
EPID2
Unit0%
X100
-
30000
Unit
Max
Values
vary
depend
ing on
the unit
setting
O
p.179
X10
-
3000.0
Unit
Max

Table of Contents