Table of Functions
490
Cod
e
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Propert
y*
Ref.
setting
Sel
1
Fire Mode
None
9
2
Test Mode
46
67
0h1D2E
Fire mode
direction
setting
Fire Mode
Dir
0
Reverse
1:
Forwar
d
O
p.32
9
1
Forward
47
68
0h1D2F
Fire mode
frequency
setting
Fire Mode
Freq
0.00max Freq
60.00
O
p.32
9
48
0h1D30
Number of
fire mode
operations
Fire Mode
Cnt
-
0
X
p.32
9
50
0h1D32
Stall
prevention
and flux
braking
Stall
Prevent
bit
00001111
0100
Δ
p.32
3
Bit 0
At
acceleration
Bit 1
At constant
speed
Bit 2
At
deceleration
Bit 3
Flux braking
51
0h1D33
Stall
frequency 1
Stall Freq
1
Start frequency-Stall
frequency2 (Hz)
60.00
O
p.32
3
52
0h1D34
Stall level 1
Stall Level
1
30-150 (%)
130
Δ
p.32
3
53
0h1D35
Stall
Stall Freq
Stall frequency1-
60.00
O
p.32
66
PRT-45 can only be set when PRT-44 is in Fire mode. To change the mode in PRT-44,
create a new password for PRT-44.
67
PRT-4647 are displayed when PRT-45 is not set to 0 (NONE)‘.
68
When Fire mode is set at PRT-45, PRT-46 is automatically set to forward, and the
frequency set at PRT-47 cannot be edited. When PRT-45 is set to Test mode, PRT-46 and
PRT-47 settings are editable.