Displayed when inverter output current exceeds
180% of the rated current.
Displayed when internal DC circuit voltage
exceeds the specified value.
Displayed when internal DC circuit voltage is less
than the specified value.
Displayed when internal DC circuit voltage is less
than the specified value during inverter operation.
Displayed when a ground fault trip occurs on the
output side of the inverter and causes the current
to exceed the specified value. The specified value
varies depending on inverter capacity.
Displayed based on inverse time-limit thermal
characteristics to prevent motor overheating.
Operates when PRT-40 is set to a value other than
‗0‘.
Displayed when a 3-phase inverter output has one
or more phases in an open circuit condition.
Operates when bit 1 of PRT-05 is set to ‗1‘.
Displayed when a 3-phase inverter input has one
or more phases in an open circuit condition.
Operates only when bit 2 of PRT-05 is set to ‗1‘.
Displayed when the inverter has been protected
from overload and resultant overheating, based on
inverse time-limit thermal characteristics. Allowable
overload rates for the inverter are 120% for 1 min
and 140% for 5 sec.
Displayed when the motor is not connected during
inverter operation. Operates when PRT-31 is set to
‗1‘.
Protection Functions Using Abnormal Internal Circuit Conditions and External
Signals
Displayed when the tempertature of the inverter
heat sink exceeds the specified value.
Displayed when the DC circuit in the inverter