Technical Specification
548
Items
Description
MMC Interlock
general operation Pre Heat
Pump Cleaning
RTC(Time Event)
Pulse
train
0–32 kHz, Low Level: 00.8 V, High Level: 3.5–12 V
Output
Multi
function
open
collector
terminal
Fault output and inverter
operation status output
Less than DC 26 V, 50 mA
Fault
signal
relay
terminal
N.O.: Less than AC 250 V
2A, DC 30 V, 3A
N.C.: Less than AC 250 V
1A, DC 30 V 1A
Multi
function
relay
terminal
Less than AC 250 V, 5 A
Less than DC 30 V, 5 A
Analog
output
0–12 Vdc(020 mA): Select frequency, output current,
output voltage, DC terminal voltage, and others.
Pulse
train
Maximum 32 kHz, 0–12 V
Protection
function
Trip
Over current trip
External signal trip
ARM short circuit current
trip
Over heat trip
Input imaging trip
Ground trip
Motor over heat trip
I/O board link trip
No motor trip
Parameter writing trip
Emergency stop trip
Command loss trip
External memory error
CPU watchdog trip
Motor under load trip
Over voltage trip
Temperature sensor trip
Inverter over heat
Option trip
Output imaging trip
Inverter overload trip
Fan trip
Low voltage trip during
operation
Low voltage trip
Analog input error
Motor overload trip
Pipe broken trip
Keypad command lost trip
Damper trip
Level Detect trip
MMC Interlock trip
PumpCleannig trip