Derating by Input Voltage
The continuous rated current of the inverter is limited based on the input voltage. Refer to
the following graph.
Derating by Ambient Temperature and Installation Type
Ambient temperature and installation type determine the constant-rated current of the
inverter. Refer to the following graph. A 2.5% current derating is applied during operation
when the ambient temperature is above 40℃. The inverter must be operated at less than
75% of its rated capacity when the ambient temperature is above 50℃.