81
Learning Basic Features
Function Codes related to HAND/AUTO/OFF Operation Modes
Codes / Functions
Description
DRV-01
Cmd Frequency
Frequency reference in AUTO mode when DRV-07 is set to‘ KeyPad‘.
DRV-02
KeyPad Run Dir
Rotation direction of the keypad command in the HAND or AUTO mode.
Settings
Description
0
Forward
Fx operation
1
Reverse
Rx operation
DRV-25
HAND Cmd Freq
Frequency displayed at the monitor display item (Monitor Line-1) when the
HAND key is pressed in other modes (default frequency reference for
HAND mode).
OUT-3136
Relay 1–5
Set AUTO State (36) to ensure that the inverter is in AUTO mode.
OUT-3136
Relay 1–5
Set HANDState (37) to ensure that the inverter is in HAND mode.
Switching between the HAND/AUTO/OFF Modes
Mode
Description
AUTOHAND
Press the HAND key in AUTO mode to switch to HAND mode. The inverter
operates as follows based on the setting at DRV-26 (Hand Ref Mode).
Settings
Description
0
Hand
Parameter
The inverter operates based on the operation direction
set at DRV-02 (Keypad Run Dir) and the frequency
reference set at DRV-25 (HAND Cmd Freq).
1
Follow
Auto
The inverter takes over the operation direction and the
frequency reference from the settings for AUTO mode
and keeps performing the same operation. If the
inverter was stopped in AUTO mode, the operation
direction is set as Fx and the frequency reference is

Table of Contents