Function Codes related to HAND/AUTO/OFF Operation Modes
Frequency reference in AUTO mode when DRV-07 is set to‘ KeyPad‘.
Rotation direction of the keypad command in the HAND or AUTO mode.
Frequency displayed at the monitor display item (Monitor Line-1) when the
HAND key is pressed in other modes (default frequency reference for
HAND mode).
Set AUTO State (36) to ensure that the inverter is in AUTO mode.
Set HANDState (37) to ensure that the inverter is in HAND mode.
Switching between the HAND/AUTO/OFF Modes
Press the HAND key in AUTO mode to switch to HAND mode. The inverter
operates as follows based on the setting at DRV-26 (Hand Ref Mode).
The inverter operates based on the operation direction
set at DRV-02 (Keypad Run Dir) and the frequency
reference set at DRV-25 (HAND Cmd Freq).
The inverter takes over the operation direction and the
frequency reference from the settings for AUTO mode
and keeps performing the same operation. If the
inverter was stopped in AUTO mode, the operation
direction is set as Fx and the frequency reference is