Pathway Technical Reference Manual
Proprietary 172 of 190
22. Appendix J – Preventive and Periodical
Maintenance
This chapter describes the preventative and periodical maintenance procedures required in
order to maintain good system performance and safety of use.
22.1 Summary Maintenance Table
The following table summarizes the required maintenance procedures.
Table 41: Summarizing Maintenance Table
Depending on usage. Perform once a
month if system is not used often
Only if system is not being used
regularly.
Requires a calibration kit. Some
study protocols may require
Thermode calibration more often
22.2 Daily Preventative Maintenance Operations
22.2.1 Visual Check
The visual check is important to ensure that all system components are intact and properly
connected before using the system.
The Visual check is required in order to make sure that there is no physical
damage to system components, particularly to the Thermodes.
1. Check all accessories and Thermodes visually.
1.1. Check that the accessory connectors are intact.
1.2. Check that the all the accessories’ bodies are intact.
1.3. Check that there is no visible damage to the Thermode heads. Check especially that
the Kapton® cover of the CHEP Thermode is intact and not peeled.
2. Make sure both Thermodes are properly connected the PATHWAY system. If your license
only includes one Thermode type (CHEPS or ATS), make sure to connect a bypass water
tube in place of the water connectors of the missing Thermode.
3. Connect all available Pathway accessories (Response Unit, Panic Button and etc.)
4. Make sure coolant level is between the minimum and maximum level (add coolant if
required, refer to section 19 for instructions).
22.2.2 Flow Rate Check
The flow rate is important to ensure the Thermodes get enough circulation of coolant for safety
and good performance. The required flow rate is approx. 37 LPH (indicator should be center