5 - 7
5 Basic Settings
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-1 Parameter Display and Parameter Initialization
5
5-1-2 Parameter Initialization
Precautions for Correct UsePrecautions for Correct Use
As a measure to prevent inadvertent parameter initialization, the Initialization Selection (b084)
and Initialization Execution (b180) settings are designed to be reset to 00 when the
initialization is completed or after power cycle. Be sure to set these parameters each time
when you need to initialize the parameter settings.
The following parameters are not initialized: the settings of the DriveProgramming User
Parameters U00 to U31 (P100 to P131), Total RUN Time Monitor (d016), Total Power ON Time
Monitor (d017), Initialization Data Selection (b085), Heavy Load/Light Load Selection (b049),
analog adjustment parameters (C081 to C083, C121 to C123), and Thermistor Adjustment
(C085).
Remember that you cannot restore the initialized data to the previous settings once you
execute parameter initialization.
The 3G3RX-V1 Series Inverter provides three controls that can be switched as required.
With a single motor, only the 1st control is used normally.
However, even with a single motor, you can use the 2nd or 3rd control to configure the settings
suitable for your application.
The 2nd or 3rd control is allocated in the 200s or 300s parameter number respectively.
For parameters with the 2nd and 3rd controls, the display changes in the order of the 1st control, the
2nd control, and the 3rd control. Therefore, when using the Digital Operator, the displayed parameter
number can change to the 200s and then the 300s.
For the explanation of the 2nd/3rd control, refer to 2nd/3rd Control Functions on page 7-111.
Clearing Fault Monitor Data
Switching among 1st, 2nd, and 3rd Controls
Step3:
Step1: Step2:
Clearing
Clear completes.
Press the Enter key to
set b084 to “01” .
Press the Enter key to
set b180 to “01” .
Clear is completed
when the clearing
display disappears.