6 - 39
6 Vector Control
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
6-6 Pulse Train Position Control Mode
6
6-6-4 Speed Bias Function
Use this function to apply speed command bias to the speed command in the pulse train position
control mode.
It adds the set speed command bias value at the start of the positioning process to enable quick
startup.
Clear the speed command bias amount before the positioning process is completed.
If the speed bias amount is added during stop, the stop position will be misaligned accordingly.
Set the bias amount in the Frequency Addition Amount Setting (A145) and the frequency addition
sign in the Frequency Addition Sign Selection (A146).
Allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to 50 (ADD: Frequency
addition).
The set bias value will be added to the speed command while the terminal ADD is ON.
6-6-4 Speed Bias Function
Parameter No. Function name Data Default data Unit
A145
Frequency Addition
Amount Setting
0.00 to 99.99
100.0 to 400.0
0.00
A146
Frequency Addition Sign
Selection
00: Add A145 value to output frequency.
01: Subtract A145 value from output
frequency.
00
C001 to C008
Multi-function Input S1 to
S8 Selection
50: ADD (Set frequency A145 addition)