4 - 7
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-1 Group A: Standard Function Parameters
4-3-1 Group A: Standard Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
A001 Frequency
Reference
Selection
00: Digital Operator (Volume
adjuster)
(Enabled when 3G3AX-OP01
is connected)
01: Control circuit terminal block
(Analog input)
02: Digital Operator (F001)
03: Modbus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: DriveProgramming
10: Operation function output
02 Disabled Disabled – 7-17
A002 RUN Command
Selection
01: Control circuit terminal block
02: Digital Operator
03: Modbus communication
04: Option 1
05: Option 2
02 Disabled Disabled – 7-18
A003 1st Base
Frequency
30. to 1st Maximum Frequency
(A004)
60. Disabled Disabled Hz 7-19
A203 2nd Base
Frequency
30. to 2nd Maximum Frequency
(A204)
60.
A303 3rd Base
Frequency
30. to 3rd Maximum Frequency
(A304)
60.
A004 1st Maximum
Frequency
30. to 400. 60. Disabled Disabled Hz 7-19
A204 2nd Maximum
Frequency
30. to 400. 60.
A304 3rd Maximum
Frequency
30. to 400. 60.