7 - 81
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-4 Detailed Functions (Group b)
7
Use the Initial Screen Selection parameter to select from the following the screen that appears on the
Digital Operator at power-ON.
By factory default, this is set to 001 (d001).
Setting the User Parameter Automatic Setting Function (b039) to 01 (Enabled) causes the inverter to
store automatically the parameters whose data have been changed in an ascending order from U001
to U012. This function is useful to keep track of changes made to the default datas.
Parameter changes are stored when the Enter key is pressed. This is also true for the monitor
functions (d***).
U001 stores the most recent parameter data; U012 stores the oldest.
The same parameter will be stored only once. In addition, attempting to store more than 12 user
parameter data results in erasing the data from the oldest (U012).
Initial Screen Selection (Initial Screen after Power-on)
Parameter No. Function name Data Default data Unit
b038 Initial Screen Selection
000: Screen on which the Enter key
was last pressed
001 to 060: d001 to d060
201: F001
202: Do not set.
001
User Parameter Automatic Setting Function
Parameter No. Function name Data Default data Unit
b039
User Parameter
Automatic Setting
Function
00: Disabled
01: Enabled
00
Related functions U001 to U012