7 Detailed Functions
7 - 14
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-2 Basic Functions (Group F)
This section describes the output frequency setting, acceleration/deceleration time, and other basic
parameters.
• Use these parameters to set the output frequency of the inverter.
• F001 can be used to set the output frequency only when the Frequency Reference Selection (A001)
is set to 02 (Digital Operator). For other frequency setting methods, refer to Frequency Reference
Selection on page 7-17. F001 functions as the frequency reference monitor when A001 is set to other
than 02.
• Setting a frequency in F001 automatically configures the 1st Multi-step Speed Reference 0 (A020) to
the same value.
To configure the 2nd/3rd control, set the 2nd Multi-step Speed Reference 0 (A220)/3rd Multi-step
Speed Reference 0 (A320), or set F001 with the SET/SET3 terminal turned ON.
To use the SET/SET3 terminal, allocate one of the Multi-function Input S1 to S8 Selection to 08
(SET)/17 (SET3).
• If the output frequency is used as the PID target value, it will be displayed as a percentage [%]. In this
case, 100% is the maximum frequency.
Output Frequency Setting/Monitor
Parameter No. Function name Data Default data Unit
F001
Output Frequency
Setting/Monitor
0.0/Starting frequency to
1st/2nd/3rd Maximum Frequency
0.0 to 100.0 (PID function enabled)
–
Hz
A020
1st Multi-step Speed
Reference 0
6.0
A220
2nd Multi-step Speed
Reference 0
*1
*1. To enable the switching to the 2nd/3rd control, allocate one of the Multi-function Input S1 to S8 Selection (C001
to C008) to 08 (SET) or 17 (SET3) and turn ON that terminal.
A320
3rd Multi-step Speed
Reference 0
*1
A001
Frequency Reference
Selection
00: Digital Operator (Volume adjuster)
01: Control circuit terminal block (Analog
input)
02: Digital Operator (F001)
03: Modbus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: DriveProgramming
10: Operation function output
02 –
Related functions C001 to C008