7 Detailed Functions
7 - 100
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Use this function to reduce the carrier frequency automatically as the output current increases.
To enable this function, set the Automatic Carrier Reduction (b089) to 01 (Enable).
When the output current exceeds 60%, 72%, 84%, and 96% of the rated current, this function
reduces the carrier frequency to 12, 9, 6, and 3 kHz, respectively.
The normal carrier frequency will be restored when the output current exceeds the carrier reduction
start level –5% (Reset level).
(Example 3) Frequency pull-in restart (b088 = 02)
When the set Restart Standby Time (b003) elapses,
the inverter starts to output at the frequency set in
the Starting Frequency Selection at Frequency
Pull-in Restart (b030).
Then, the inverter decelerates the motor according
to the Frequency Pull-in Restart Parameter (b029)
setting, while suppressing the output current to the
value set in the Frequency Pull-in Restart Level
(b028).
When the current decreases to or below the
Frequency Pull-in Restart Level (b028), the inverter
accelerates the motor again to return to the original
frequency.
If this method causes an overcurrent trip, decrease
the value set in the Frequency Pull-in Restart Level
(b028).
Automatic Carrier Frequency Reduction Function
Parameter No. Function name Data Default data Unit
b089
Automatic Carrier
Reduction
00: Disabled
01: Enabled, dependent on the current
00
Carrier reduction start level (Reset level) Reduced carrier frequency (kHz)
Less than 60% of rated current 15.0
60% (55%) of rated current 12.0
72% (67%) of rated current 9.0
84% (79%) of rated current 6.0
96% (91%) of rated current 3.0
FW input
(Forward)
FRS input
Output
current
Inverter output
frequency
Motor rpm
Decelerates
according to b029
Frequency selected
in b030
b028
b003