4 - 19
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-2 Group b: Detailed Function Parameters
*1 The default data was changed from the previous model.
4-3-2 Group b: Detailed Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
b001 Power
Interruption/Under
voltage Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
00 Disabled Enabled – 7-61
b002 Allowable Power
Interruption Time
0.3 to 25.0 1.0 Disabled Enabled s
b003 Restart Standby
Time
0.3 to 100.0 1.0 Disabled Enabled s
b004 Power
Interruption/Under
voltage Trip
Selection During
Stop
00: Disabled
01: Enabled
02: Disabled during stop and
deceleration stop
00 Disabled Enabled –
b005 Power Interruption
Restart Count
00: 16 times
01: No limit
00 Disabled Enabled –
b006 Input Phase Loss
Protection
Selection
00: Disabled
01: Enabled
01
*1
Disabled Enabled – 7-65
b007 Frequency
Matching Lower
Limit Frequency
0.00 to 99.99
100.0 to 400.0
0.00 Disabled Enabled Hz 7-61
b008 Overvoltage/Over
current Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
00 Disabled Enabled –
b009 Undervoltage
Restart Count
00: 16 times
01: No limit
00 Disabled Enabled –
b010 Overvoltage/Over
current Restart
Count
1 to 3 3 Disabled Enabled time
b011 Overvoltage/Over
current Restart
Standby Time
0.3 to 100.0 1.0 Disabled Enabled s