Omron RX Series - Group B: Detailed Function Parameters

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 - 19
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-2 Group b: Detailed Function Parameters
*1 The default data was changed from the previous model.
4-3-2 Group b: Detailed Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
b001 Power
Interruption/Under
voltage Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
00 Disabled Enabled 7-61
b002 Allowable Power
Interruption Time
0.3 to 25.0 1.0 Disabled Enabled s
b003 Restart Standby
Time
0.3 to 100.0 1.0 Disabled Enabled s
b004 Power
Interruption/Under
voltage Trip
Selection During
Stop
00: Disabled
01: Enabled
02: Disabled during stop and
deceleration stop
00 Disabled Enabled
b005 Power Interruption
Restart Count
00: 16 times
01: No limit
00 Disabled Enabled
b006 Input Phase Loss
Protection
Selection
00: Disabled
01: Enabled
01
*1
Disabled Enabled 7-65
b007 Frequency
Matching Lower
Limit Frequency
0.00 to 99.99
100.0 to 400.0
0.00 Disabled Enabled Hz 7-61
b008 Overvoltage/Over
current Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
00 Disabled Enabled
b009 Undervoltage
Restart Count
00: 16 times
01: No limit
00 Disabled Enabled
b010 Overvoltage/Over
current Restart
Count
1 to 3 3 Disabled Enabled time
b011 Overvoltage/Over
current Restart
Standby Time
0.3 to 100.0 1.0 Disabled Enabled s
Momentary power interruption/Trip restart